If the engine oil pressure drops to an unsafe level during operation, the oil pressure monitor lamp will
flash, and the engine will automatically shut down. If this occurs, check the engine oil level, and refill to
the maximum level if needed.
<Caution>
The engine oil pressure monitor cannot detect the degradation of the engine oil itself. Check the
engine oil periodically, and change it according to the manufacturer’s recommendation. (Refer to
Section 11 Maintenance.)
Overheat Monitor Lamp
If this equipment is used at a capacity
that exceeds its rating, it will automatically
reduce the output to a satisfactory level and
the OVERHEAT monitor lamp will flash.
FLASH OVERHEAT
The OVERHEAT monitor lamp will also flash
if the machine is being used in excess of
its rated duty cycle.
When the OVERHEAT monitor activates,
the AC generator is not usable.
If the engine automatically shuts down and none of the monitor lamps are lit to indicate why it has
shut down, check the 20 amp and 50 amp fuses located above the battery inside at the top of the
enclosure. If either of these fuses is burned out, there is an electrical problem of some kind.
Investigate the cause and correct it prior to trying to restart this equipment.
7-6. Earth Leakage Relay
Danger: Electric Shock
Both grounding terminals of this equipment should be earth grounded prior to the operation of the
equipment.
Even though all the terminals of the loads may be grounded, the earth grounding terminal and the
enclosure grounding terminal should be earth grounded.
Grounding connections should be made only when the engine is stopped.
If the earth leakage relay activates, determine the cause for the relay activation and correct it
before restarting this equipment.
This equipment is provided with an earth leakage relay in the AC Circuit Breaker to detect current
leakage to ground on the loads it is supplying. This circuit breaker will trip upon detecting excess current
to ground to protect the operator(s) from possible electric shock.
The earth leakage relay is rated:
Sensitive Current: 30mA (or less)
(Grounding resistance: 500 ohms or less)
Sensitive time: Within 0.1 second